NYC Sprinkler Piping Color Coding

Sprinkler piping is painted so that firefighters, inspectors and building staff can quickly identify fire and life safety systems. The painting requirements are located in section 903.6 of the 2025 NYC Building Code. There are different requirements for new construction, alterations and existing buildings as will be discussed forward the end of this article.

What is required to be painted?

Dedicated sprinkler piping must be painted abiding by the following scheme.

  • Risers and cross connections: red
  • Valve handles on dedicated sprinkler systems: green
  • Valve handles on combination standpipe/sprinkler systems: yellow. Risers and cross connections that also serve the standpipe stay red.

What doesn’t need to be painted?

  • Attachments, gauges, valves and other operable parts of the system other than valve handled as noted above.
  • Horizontal branch lines
  • Facilities storing, handling or using flammable and combustible liquids, where Section 3406 of the NYC Fire Code may require different color coding

Branch lines do not need to be painted. A branch line is typically defined as piping that is either:

  • Downstream of a floor control valves
  • Where no floor control valves are present, piping that runs horizontally and directly connects to sprinkler heads

Branch piping may be painting any color preferred by the tenant.

The DOB’s Skilled Trades Project Requirements: Sprinkler Work & Inspections page gives a brief summary of the color coding requirements in one table.

When Does Painting Apply?

Based on the type of work being done the painting requirements trigger at different timing.

Work TypeCode sectionWhat gets paintedWhen
New buildings903.6.1Risers and cross connections red; dedicated sprinkler valve handles greenBefore the hydrostatic pressure test, even if the piping will later be enclosed
Alterations903.6.2Risers and cross connections of existing stand-alone sprinkler systems that are exposed during the work red; valve handles greenBefore the hydrostatic test, if the alteration requires one
Completed buildings903.6.3All exposed risers and cross connections red; all sprinkler valve handles greenRetroactive for buildings existing on March 2, 2010